 "version": "2026-10-20",
 "license": "Dimension sheets: CC BY 4.0. Standard and published-size files: CC BY 4.0. Xem Studio's own designs (files_license = Xem Studio Design License): free to use and sell things from, not to redistribute as files — https://xemstudio.com/license/. Other publishers' files: their own license, linked beside them.",
 "slug": "pvc-rigid-conduit-sch-40-80-nema-tc-2",
 "name": "PVC rigid conduit Schedule 40 and Schedule 80 (NEMA TC 2 / UL 651): trade size, OD, minimum wall, minimum average ID, 1/2 to 8 in + 100 mm sections",
 "kind": "standard",
 "category": "Tri-clamp & pipe",
 "group": "Pipe, tube & threads",
 "year": null,
 "question": "What are the OD and minimum wall of Schedule 40 and Schedule 80 PVC conduit (1/2 to 6 in)?",
 "tags": [
  "pvc conduit",
  "electrical conduit",
  "schedule 40 conduit",
  "schedule 80 conduit",
  "nema tc 2",
  "ul 651",
  "rigid pvc conduit",
  "conduit od",
  "conduit trade size",
  "hollow section"
 ],
 "aliases": [
  "schedule 40 pvc conduit od",
  "1 inch pvc conduit outside diameter",
  "2 inch pvc conduit od",
  "schedule 80 pvc conduit wall",
  "pvc conduit 3 inch od",
  "pvc conduit trade size chart",
  "1/2 pvc conduit od",
  "4 inch pvc conduit od wall",
  "nema tc 2 conduit dimensions",
  "sch 80 pvc conduit 1 inch wall",
  "pvc conduit id sch 40 2 inch",
  "pvc conduit 6 inch od",
  "ul 651 conduit sizes"
 ],
 "overall_mm": {
  "length": 168.27,
  "width": 168.27,
  "height": 100
 },
 "official_cad": false,
 "xem_status": "free-files",
 "les": false,
 "free_files": 16,
 "url": "https://xemstudio.com/objects/pvc-rigid-conduit-sch-40-80-nema-tc-2/",
 "sheet_txt": "https://xemstudio.com/objects/pvc-rigid-conduit-sch-40-80-nema-tc-2/sheet.txt",
 "sheet": {
  "basis": "Wheatland Tube's PVC conduit spec sheet (Sch 40 and 80, 1/2 to 4 in) and Atkore's Sch 40 spec (1/2 to 8 in) agree on OD, minimum wall and minimum average ID; walls for 6 and 8 in Sch 80 are from a PVC conduit manufacturer's page",
  "overall_mm": {
   "length": 168.27,
   "width": 168.27,
   "height": 100
  },
  "notes": [
   "PVC rigid conduit is made to the same trade sizes and outside diameters as PVC and steel pipe, so a Schedule 40 or 80 PVC conduit has the OD of the matching NPS pipe (1/2 in 0.840, 3/4 in 1.050, 1 in 1.315, 1-1/4 in 1.660, 1-1/2 in 1.900, 2 in 2.375, 2-1/2 in 2.875, 3 in 3.500, 3-1/2 in 4.000, 4 in 4.500, 5 in 5.563, 6 in 6.625, 8 in 8.625). Wheatland's sheet cites UL 651 and lists NEMA TC 2 and ASTM 1784 among its standards; Atkore's names UL 651, which does not include the 8 in size (as Atkore says). The standards themselves were not read; the numbers are the two makers' sheets.",
   "Walls are minimum walls and the IDs are minimum average IDs, not nominal: ID = OD − 2 × minimum wall (shown separately, the last numeric column) is larger than the printed minimum average ID (for example 1/2 in Sch 40: 0.622 against 0.578 in), because the OD and wall tolerances are applied. Wheatland and Atkore print identical Schedule 40 numbers for 1/2 to 4 in; Atkore adds 5 in (OD 5.563, wall 0.258, ID 4.975), 6 in (6.625, 0.280, 5.986) and 8 in (8.625, 0.322, 7.853).",
   "Schedule 80 (heavier wall, same OD): Wheatland prints 1/2 to 4 in; its minimum average ID for 3-1/2 in (3.820) is larger than the one for 4 in (3.737) and than OD − 2 × wall (3.364), so it is almost certainly a typo and is left blank here. 6 and 8 in Sch 80 walls (0.432, 0.500) are from a PVC conduit manufacturer's page, a second source for the other Sch 80 walls (equal at every size that page lists: 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 3 and 4 in); that page's ID columns (for example 0.824 in for 3/4 in Sch 40, against Wheatland and Atkore's 0.780) are different quantities and are not used. No Sch 80 data for 5 in was read.",
   "Not covered: Type EB and DB (encased burial / direct burial) conduit, fittings (sockets, elbows), and the PVC pipe tables, which are on pvc-schedule-40-80-pipe-od-and-wall and schedule-40-pipe (1/2 to 2 in Sch 40 pipe sections). Steel conduit: rigid-imc-emt-conduit-sizes-to-4-in and emt-conduit; flexible and liquid-tight metal conduit: flexible-metal-conduit-fmc-lfmc-trade-sizes.",
   "Files: 100 mm hollow sections at the average OD and the minimum wall: Schedule 40 for 2-1/2, 3, 3-1/2, 4, 5 and 6 in (1/2 to 2 in Schedule 40 is on schedule-40-pipe) and Schedule 80 for 1/2 to 4 in. The length is Xem's example length; actual conduit ID varies with the tolerances above."
  ],
  "table": {
   "columns": [
    "schedule",
    "trade size, in",
    "average OD, in",
    "OD, mm",
    "minimum wall, in",
    "minimum wall, mm",
    "min. average ID, in",
    "min. average ID, mm",
    "OD − 2 × min. wall, in"
   ],
   "rows": [
    [
     "Schedule 40",
     "1/2",
     "0.840",
     "21.34",
     "0.109",
     "2.77",
     "0.578",
     "14.68",
     "0.622"
    ],
    [
     "Schedule 40",
     "3/4",
     "1.050",
     "26.67",
     "0.113",
     "2.87",
     "0.780",
     "19.81",
     "0.824"
    ],
    [
     "Schedule 40",
     "1",
     "1.315",
     "33.40",
     "0.133",
     "3.38",
     "1.004",
     "25.50",
     "1.049"
    ],
    [
     "Schedule 40",
     "1-1/4",
     "1.660",
     "42.16",
     "0.140",
     "3.56",
     "1.335",
     "33.91",
     "1.380"
    ],
    [
     "Schedule 40",
     "1-1/2",
     "1.900",
     "48.26",
     "0.145",
     "3.68",
     "1.564",
     "39.73",
     "1.610"
    ],
    [
     "Schedule 40",
     "2",
     "2.375",
     "60.33",
     "0.154",
     "3.91",
     "2.021",
     "51.33",
     "2.067"
    ],
    [
     "Schedule 40",
     "2-1/2",
     "2.875",
     "73.03",
     "0.203",
     "5.16",
     "2.414",
     "61.32",
     "2.469"
    ],
    [
     "Schedule 40",
     "3",
     "3.500",
     "88.90",
     "0.216",
     "5.49",
     "3.008",
     "76.40",
     "3.068"
    ],
    [
     "Schedule 40",
     "3-1/2",
     "4.000",
     "101.60",
     "0.226",
     "5.74",
     "3.486",
     "88.54",
     "3.548"
    ],
    [
     "Schedule 40",
     "4",
     "4.500",
     "114.30",
     "0.237",
     "6.02",
     "3.961",
     "100.61",
     "4.026"
    ],
    [
     "Schedule 40",
     "5",
     "5.563",
     "141.30",
     "0.258",
     "6.55",
     "4.975",
     "126.37",
     "5.047"
    ],
    [
     "Schedule 40",
     "6",
     "6.625",
     "168.28",
     "0.280",
     "7.11",
     "5.986",
     "152.04",
     "6.065"
    ],
    [
     "Schedule 40",
     "8",
     "8.625",
     "219.08",
     "0.322",
     "8.18",
     "7.853",
     "199.47",
     "7.981"
    ],
    [
     "Schedule 80",
     "1/2",
     "0.840",
     "21.34",
     "0.147",
     "3.73",
     "0.502",
     "12.75",
     "0.546"
    ],
    [
     "Schedule 80",
     "3/4",
     "1.050",
     "26.67",
     "0.154",
     "3.91",
     "0.608",
     "15.44",
     "0.742"
    ],
    [
     "Schedule 80",
     "1",
     "1.315",
     "33.40",
     "0.179",
     "4.55",
     "0.910",
     "23.11",
     "0.957"
    ],
    [
     "Schedule 80",
     "1-1/4",
     "1.660",
     "42.16",
     "0.191",
     "4.85",
     "1.227",
     "31.17",
     "1.278"
    ],
    [
     "Schedule 80",
     "1-1/2",
     "1.900",
     "48.26",
     "0.200",
     "5.08",
     "1.446",
     "36.73",
     "1.500"
    ],
    [
     "Schedule 80",
     "2",
     "2.375",
     "60.33",
     "0.218",
     "5.54",
     "1.881",
     "47.78",
     "1.939"
    ],
    [
     "Schedule 80",
     "2-1/2",
     "2.875",
     "73.03",
     "0.276",
     "7.01",
     "2.250",
     "57.15",
     "2.323"
    ],
    [
     "Schedule 80",
     "3",
     "3.500",
     "88.90",
     "0.300",
     "7.62",
     "2.820",
     "71.63",
     "2.900"
    ],
    [
     "Schedule 80",
     "3-1/2",
     "4.000",
     "101.60",
     "0.318",
     "8.08",
     "—",
     "—",
     "3.364"
    ],
    [
     "Schedule 80",
     "4",
     "4.500",
     "114.30",
     "0.337",
     "8.56",
     "3.737",
     "94.92",
     "3.826"
    ],
    [
     "Schedule 80",
     "6",
     "6.625",
     "168.28",
     "0.432",
     "10.97",
     "—",
     "—",
     "5.761"
    ],
    [
     "Schedule 80",
     "8",
     "8.625",
     "219.08",
     "0.500",
     "12.70",
     "—",
     "—",
     "7.625"
    ]
   ]
  }
 },
 "sheet_text": "PVC rigid conduit Schedule 40 and Schedule 80 (NEMA TC 2 / UL 651): trade size, OD, minimum wall, minimum average ID, 1/2 to 8 in + 100 mm sections — dimension sheet\nSource: Xem Studio, https://xemstudio.com/objects/pvc-rigid-conduit-sch-40-80-nema-tc-2/  (sheet CC BY 4.0)\nBasis: Wheatland Tube's PVC conduit spec sheet (Sch 40 and 80, 1/2 to 4 in) and Atkore's Sch 40 spec (1/2 to 8 in) agree on OD, minimum wall and minimum average ID; walls for 6 and 8 in Sch 80 are from a PVC conduit manufacturer's page\nCatalog version: 2026-10-20\n\nOverall (mm): length 168.27, width 168.27, height 100.0\n- PVC rigid conduit is made to the same trade sizes and outside diameters as PVC and steel pipe, so a Schedule 40 or 80 PVC conduit has the OD of the matching NPS pipe (1/2 in 0.840, 3/4 in 1.050, 1 in 1.315, 1-1/4 in 1.660, 1-1/2 in 1.900, 2 in 2.375, 2-1/2 in 2.875, 3 in 3.500, 3-1/2 in 4.000, 4 in 4.500, 5 in 5.563, 6 in 6.625, 8 in 8.625). Wheatland's sheet cites UL 651 and lists NEMA TC 2 and ASTM 1784 among its standards; Atkore's names UL 651, which does not include the 8 in size (as Atkore says). The standards themselves were not read; the numbers are the two makers' sheets.\n- Walls are minimum walls and the IDs are minimum average IDs, not nominal: ID = OD − 2 × minimum wall (shown separately, the last numeric column) is larger than the printed minimum average ID (for example 1/2 in Sch 40: 0.622 against 0.578 in), because the OD and wall tolerances are applied. Wheatland and Atkore print identical Schedule 40 numbers for 1/2 to 4 in; Atkore adds 5 in (OD 5.563, wall 0.258, ID 4.975), 6 in (6.625, 0.280, 5.986) and 8 in (8.625, 0.322, 7.853).\n- Schedule 80 (heavier wall, same OD): Wheatland prints 1/2 to 4 in; its minimum average ID for 3-1/2 in (3.820) is larger than the one for 4 in (3.737) and than OD − 2 × wall (3.364), so it is almost certainly a typo and is left blank here. 6 and 8 in Sch 80 walls (0.432, 0.500) are from a PVC conduit manufacturer's page, a second source for the other Sch 80 walls (equal at every size that page lists: 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 3 and 4 in); that page's ID columns (for example 0.824 in for 3/4 in Sch 40, against Wheatland and Atkore's 0.780) are different quantities and are not used. No Sch 80 data for 5 in was read.\n- Not covered: Type EB and DB (encased burial / direct burial) conduit, fittings (sockets, elbows), and the PVC pipe tables, which are on pvc-schedule-40-80-pipe-od-and-wall and schedule-40-pipe (1/2 to 2 in Sch 40 pipe sections). Steel conduit: rigid-imc-emt-conduit-sizes-to-4-in and emt-conduit; flexible and liquid-tight metal conduit: flexible-metal-conduit-fmc-lfmc-trade-sizes.\n- Files: 100 mm hollow sections at the average OD and the minimum wall: Schedule 40 for 2-1/2, 3, 3-1/2, 4, 5 and 6 in (1/2 to 2 in Schedule 40 is on schedule-40-pipe) and Schedule 80 for 1/2 to 4 in. The length is Xem's example length; actual conduit ID varies with the tolerances above.\n\nschedule  trade size, in  average OD, in  OD, mm  minimum wall, in  minimum wall, mm  min. average ID, in  min. average ID, mm  OD − 2 × min. wall, in\nSchedule 40  1/2  0.840  21.34  0.109  2.77  0.578  14.68  0.622\nSchedule 40  3/4  1.050  26.67  0.113  2.87  0.780  19.81  0.824\nSchedule 40  1  1.315  33.40  0.133  3.38  1.004  25.50  1.049\nSchedule 40  1-1/4  1.660  42.16  0.140  3.56  1.335  33.91  1.380\nSchedule 40  1-1/2  1.900  48.26  0.145  3.68  1.564  39.73  1.610\nSchedule 40  2  2.375  60.33  0.154  3.91  2.021  51.33  2.067\nSchedule 40  2-1/2  2.875  73.03  0.203  5.16  2.414  61.32  2.469\nSchedule 40  3  3.500  88.90  0.216  5.49  3.008  76.40  3.068\nSchedule 40  3-1/2  4.000  101.60  0.226  5.74  3.486  88.54  3.548\nSchedule 40  4  4.500  114.30  0.237  6.02  3.961  100.61  4.026\nSchedule 40  5  5.563  141.30  0.258  6.55  4.975  126.37  5.047\nSchedule 40  6  6.625  168.28  0.280  7.11  5.986  152.04  6.065\nSchedule 40  8  8.625  219.08  0.322  8.18  7.853  199.47  7.981\nSchedule 80  1/2  0.840  21.34  0.147  3.73  0.502  12.75  0.546\nSchedule 80  3/4  1.050  26.67  0.154  3.91  0.608  15.44  0.742\nSchedule 80  1  1.315  33.40  0.179  4.55  0.910  23.11  0.957\nSchedule 80  1-1/4  1.660  42.16  0.191  4.85  1.227  31.17  1.278\nSchedule 80  1-1/2  1.900  48.26  0.200  5.08  1.446  36.73  1.500\nSchedule 80  2  2.375  60.33  0.218  5.54  1.881  47.78  1.939\nSchedule 80  2-1/2  2.875  73.03  0.276  7.01  2.250  57.15  2.323\nSchedule 80  3  3.500  88.90  0.300  7.62  2.820  71.63  2.900\nSchedule 80  3-1/2  4.000  101.60  0.318  8.08  —  —  3.364\nSchedule 80  4  4.500  114.30  0.337  8.56  3.737  94.92  3.826\nSchedule 80  6  6.625  168.28  0.432  10.97  —  —  5.761\nSchedule 80  8  8.625  219.08  0.500  12.70  —  —  7.625\n\nFiles elsewhere (not hosted by Xem Studio; license as stated by the publisher):\n- Wheatland Tube: PVC conduit specifications: Schedule 40 and Schedule 80, 1/2 to 4 in: average OD, minimum wall, minimum average ID — web — Maker spec sheet; numbers only — https://wheatland.com/wp-content/uploads/2024/10/PVC-Conduit-Specifications.pdf\n- Atkore: PVC rigid Schedule 40 conduit (spec ATCE-SPEC-6709-2402): average OD, minimum wall, ID, 1/2 to 8 in — web — Distributor-hosted maker spec; numbers only — https://www.elliottelectric.com/Media/PVC6-PVC\n- PVC conduit manufacturer (pvcconduitmanufacturer.com): PVC electrical conduit sizes: OD, Schedule 40 / 80 minimum wall and average ID, 1/2 to 8 in — web — Maker page; numbers only. Its ID columns differ from the Wheatland / Atkore sheets and are not used — https://www.pvcconduitmanufacturer.com/?p=9414\n\nFree files (CC BY 4.0, Xem Studio; STEP + STL, 16 parts): https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/index.json\nAPI: https://xemstudio.com/api/geometry?object=pvc-rigid-conduit-sch-40-80-nema-tc-2\n",
 "sources": [
  {
   "publisher": "Wheatland Tube",
   "title": "PVC conduit specifications: Schedule 40 and Schedule 80, 1/2 to 4 in: average OD, minimum wall, minimum average ID",
   "url": "https://wheatland.com/wp-content/uploads/2024/10/PVC-Conduit-Specifications.pdf",
   "formats": [
    "web"
   ],
   "license": "Maker spec sheet; numbers only",
   "license_verified": true,
   "hosted": false
  },
  {
   "publisher": "Atkore",
   "title": "PVC rigid Schedule 40 conduit (spec ATCE-SPEC-6709-2402): average OD, minimum wall, ID, 1/2 to 8 in",
   "url": "https://www.elliottelectric.com/Media/PVC6-PVC",
   "formats": [
    "web"
   ],
   "license": "Distributor-hosted maker spec; numbers only",
   "license_verified": true,
   "hosted": false
  },
  {
   "publisher": "PVC conduit manufacturer (pvcconduitmanufacturer.com)",
   "title": "PVC electrical conduit sizes: OD, Schedule 40 / 80 minimum wall and average ID, 1/2 to 8 in",
   "url": "https://www.pvcconduitmanufacturer.com/?p=9414",
   "formats": [
    "web"
   ],
   "license": "Maker page; numbers only. Its ID columns differ from the Wheatland / Atkore sheets and are not used",
   "license_verified": true,
   "hosted": false
  }
 ],
 "xem": {
  "status": "free-files",
  "sheet_free": true,
  "mesh_price_usd": null,
  "step_price_usd": null,
  "tolerance_mm": null
 },
 "related": [
  "pvc-schedule-40-80-pipe-od-and-wall",
  "schedule-40-pipe",
  "rigid-imc-emt-conduit-sizes-to-4-in",
  "emt-conduit",
  "flexible-metal-conduit-fmc-lfmc-trade-sizes",
  "conduit-knockout-diameters-nema-bulletin-71",
  "metal-boxes-us"
 ],
 "fits": [],
 "dimensions": "exact (nominal, no tolerance added)",
 "dimension_rule": "All geometry on Xem Studio is exact (nominal, true size) with no tolerance added. Where a part meets another part, the object lists its mating features (feature, exact size, what it mates with, fit class: press, slide, run, socket, clamp or designed). Apply your process's allowance to those features only; 'designed' gaps are part of the design and stay as drawn. Typical accuracy by process and ISO 286 fits: https://xemstudio.com/tolerances/",
 "mating": [
  {
   "feature": "conduit OD",
   "exact": "Sch 40: 2-1/2 in 73.03, 3 in 88.90, 3-1/2 in 101.60, 4 in 114.30, 5 in 141.30, 6 in 168.28 mm; Sch 80: 1/2 in 21.34, 3/4 in 26.67, 1 in 33.40, 1-1/4 in 42.16, 1-1/2 in 48.26, 2 in 60.33, 2-1/2 in 73.03, 3 in 88.90, 3-1/2 in 101.60, 4 in 114.30 mm (average OD)",
   "mates": "socket of a PVC conduit coupling or fitting, the same OD as PVC pipe (schedule-40-pipe, pvc-schedule-40-fittings-laying-lengths); the socket bore is the OD plus your solvent-cement clearance",
   "fit": "socket",
   "files": "pvc-conduit-"
  }
 ],
 "fit_classes": {
  "press": "stays put: pin, tube, bearing or magnet held by interference. ISO 286 equivalent: H7/p6 (locational interference) or tighter.",
  "slide": "assembles by hand and is held by a grub, pinch or clamp: shaft in a hub, rod in a socket, spigot in a bore. ISO 286 equivalent: H7/g6 or H7/h6.",
  "run": "turns or slides in use: pin in a link, rod through a guide. ISO 286 equivalent: H8/f7 (close running).",
  "socket": "large sliding fit: syringe barrel, sleeve, bobbin in a bore. ISO 286 equivalent: H9/d9 (free running) or looser.",
  "clamp": "split part that closes on the mating part with screws: make it at size.",
  "designed": "a gap that is part of the design (piston fit option, displacer gap, air gap): do not change."
 },
 "faq": [
  {
   "q": "What is the OD of 1 inch PVC conduit?",
   "a": "1.315 in (33.40 mm) for Schedule 40 and Schedule 80; the minimum wall is 0.133 in (Sch 40) and 0.179 in (Sch 80)."
  },
  {
   "q": "What is the difference between Schedule 40 and 80 PVC conduit?",
   "a": "Same OD; Schedule 80 has the thicker wall: at 2 in 0.218 against 0.154 in."
  },
  {
   "q": "What is the OD of 4 inch PVC conduit?",
   "a": "4.500 in (114.30 mm); minimum wall 0.237 in (Sch 40) or 0.337 in (Sch 80)."
  }
 ],
 "files_license": null,
 "offers": [
  {
   "file": "pvc-conduit-sch40-2-1-2in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-2-1-2in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-2-1-2in-100mm.stl",
   "note": "PVC conduit Schedule 40, trade size 2-1/2 in: average OD and minimum wall: OD Ø73.03, wall 5.156, bore Ø62.71, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch40-3in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-3in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-3in-100mm.stl",
   "note": "PVC conduit Schedule 40, trade size 3 in: average OD and minimum wall: OD Ø88.90, wall 5.486, bore Ø77.93, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch40-3-1-2in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-3-1-2in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-3-1-2in-100mm.stl",
   "note": "PVC conduit Schedule 40, trade size 3-1/2 in: average OD and minimum wall: OD Ø101.60, wall 5.740, bore Ø90.12, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch40-4in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-4in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-4in-100mm.stl",
   "note": "PVC conduit Schedule 40, trade size 4 in: average OD and minimum wall: OD Ø114.30, wall 6.020, bore Ø102.26, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch40-5in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-5in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-5in-100mm.stl",
   "note": "PVC conduit Schedule 40, trade size 5 in: average OD and minimum wall: OD Ø141.30, wall 6.553, bore Ø128.19, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch40-6in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-6in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch40-6in-100mm.stl",
   "note": "PVC conduit Schedule 40, trade size 6 in: average OD and minimum wall: OD Ø168.28, wall 7.112, bore Ø154.05, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-1-2in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-1-2in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-1-2in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 1/2 in: average OD and minimum wall: OD Ø21.34, wall 3.734, bore Ø13.87, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-3-4in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-3-4in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-3-4in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 3/4 in: average OD and minimum wall: OD Ø26.67, wall 3.912, bore Ø18.85, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-1in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-1in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-1in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 1 in: average OD and minimum wall: OD Ø33.40, wall 4.547, bore Ø24.31, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-1-1-4in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-1-1-4in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-1-1-4in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 1-1/4 in: average OD and minimum wall: OD Ø42.16, wall 4.851, bore Ø32.46, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-1-1-2in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-1-1-2in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-1-1-2in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 1-1/2 in: average OD and minimum wall: OD Ø48.26, wall 5.080, bore Ø38.10, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-2in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-2in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-2in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 2 in: average OD and minimum wall: OD Ø60.33, wall 5.537, bore Ø49.25, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-2-1-2in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-2-1-2in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-2-1-2in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 2-1/2 in: average OD and minimum wall: OD Ø73.03, wall 7.010, bore Ø59.00, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-3in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-3in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-3in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 3 in: average OD and minimum wall: OD Ø88.90, wall 7.620, bore Ø73.66, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-3-1-2in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-3-1-2in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-3-1-2in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 3-1/2 in: average OD and minimum wall: OD Ø101.60, wall 8.077, bore Ø85.45, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  },
  {
   "file": "pvc-conduit-sch80-4in-100mm",
   "formats": [
    "step",
    "stl"
   ],
   "price_usd": 0,
   "license": "CC BY 4.0 (Xem Studio)",
   "step": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-4in-100mm.step",
   "stl": "https://xemstudio.com/files/hardware/pvc-rigid-conduit-sch-40-80-nema-tc-2/pvc-conduit-sch80-4in-100mm.stl",
   "note": "PVC conduit Schedule 80, trade size 4 in: average OD and minimum wall: OD Ø114.30, wall 8.560, bore Ø97.18, 100 mm long (Xem's example length; cut to the length you need); plain hollow section, no ends, seam or finish"
  }
 ],
 "markdown": "https://xemstudio.com/objects/pvc-rigid-conduit-sch-40-80-nema-tc-2/index.md"
}