Metric wire sizes (IEC 60228): 0.5 to 2500 mm² with strands and conductor diameter, and the nearest AWG

What diameter is a 1.5 mm² or 2.5 mm² conductor, and what AWG is closest? · Standard part · basis: IEC 60228 size list (Wikipedia / Wikiwand) and myElectrical's metric-to-AWG construction table, every row machine-checked; numbers only

Also called: 1.5 mm2 wire diameter, 2.5 mm2 to awg, mm2 to awg, 4mm2 wire diameter, 1 mm2 wire diameter, 0.75 mm2 to awg, iec 60228 sizes, 6mm2 cable diameter, 10 mm2 conductor diameter, metric wire size chart, mm2 wire sizes list, 2.5mm2 stranded conductor diameter

Exact dimensions. True size, with no tolerance added.

sizes
34 in table

Notes

  • IEC 60228 conductor sizes (nominal cross-sections, mm²) as listed on Wikipedia / Wikiwand: 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630, 800, 1000, 1200, 1400, 1600, 1800, 2000, 2500 (1400 and 1800 are marked non-preferred there). Classes: 1 solid, 2 stranded for fixed installation, 5 flexible, 6 very flexible. The standard also sets maximum conductor resistance (Ω/km) per size, class and type, and maximum diameters for each class; neither was in a source that could be read, so neither is on this page.
  • The table is myElectrical's metric-to-AWG table, rows for the metric sizes only: solid or stranded construction, the diameter of the wire or of each strand and the overall conductor diameter. That page says it has not checked its tables against the standard, and its AWG-row for 1 AWG prints 9.43 mm for 0.332 in (that is 8.43 mm), so Xem checks every row: the overall diameter must equal strands across × strand diameter (1 across for solid, 7 strands 3, 19 strands 5, 37 strands 7, 61 strands 9, 91 strands 11). All 34 rows listed pass. Stranding numbers describe one common construction, not the only one the standard allows.
  • The 625 mm² row appears in myElectrical's table but 625 is not among the IEC 60228 sizes read (630 is); it is kept as printed and marked.
  • Insulated cable outside diameters depend on insulation, class and maker: no maker table that could be read is on this page. Typical cord OD numbers are on the cable-and-plug-sizes page.
  • AWG sizes and diameters: see the AWG page (ASTM B258). From the ASTM B258 areas: 0.5 mm² lies between 20 AWG (0.519 mm²) and 21 AWG (0.412 mm²); 0.75 mm² lies between 18 AWG (0.823 mm²) and 19 AWG (0.653 mm²); 1 mm² lies between 17 AWG (1.04 mm²) and 18 AWG (0.823 mm²); 1.5 mm² lies between 15 AWG (1.65 mm²) and 16 AWG (1.31 mm²); 2.5 mm² lies between 13 AWG (2.63 mm²) and 14 AWG (2.08 mm²); 4 mm² lies between 11 AWG (4.17 mm²) and 12 AWG (3.31 mm²); 6 mm² lies between 9 AWG (6.63 mm²) and 10 AWG (5.26 mm²); 10 mm² lies between 7 AWG (10.6 mm²) and 8 AWG (8.37 mm²); 16 mm² lies between 5 AWG (16.8 mm²) and 6 AWG (13.3 mm²); 25 mm² lies between 3 AWG (26.7 mm²) and 4 AWG (21.1 mm²). These are nearest-size comparisons by area, not equivalences for current rating.

Metric wire sizes (IEC 60228): 0.5 to 2500 mm² with strands and… size chart

conductor mm²construction (source's table)wire / strand diameter (mm)overall conductor diameter (mm)a size listed for IEC 60228
0.5solid0.8130.81yes
0.75solid0.9910.99yes
1solid1.141.14yes
17 strands0.4321.3yes
1.5solid1.401.4yes
1.57 strands0.5331.6yes
2.5solid1.801.8yes
2.57 strands0.6862.06yes
4solid2.262.26yes
47 strands0.8642.59yes
6solid2.772.77yes
67 strands1.073.21yes
10solid3.583.58yes
107 strands1.374.12yes
167 strands1.735.18yes
257 strands2.166.48yes
2519 strands1.326.6yes
357 strands2.547.62yes
3519 strands1.557.75yes
5019 strands1.859.27yes
7019 strands2.1810.9yes
9519 strands2.5712.8yes
9537 strands1.8312.8yes
12037 strands2.0614.4yes
15037 strands2.2916yes
18537 strands2.5417.8yes
24037 strands2.9020.3yes
24061 strands2.2620.3yes
30061 strands2.5122.6yes
40061 strands2.9026.1yes
50061 strands3.2529.3yes
62591 strands2.9732.7no (in the source table, not in the 30 IEC 60228 sizes read)
80091 strands3.3536.9yes
100091 strands3.7341.1yes

Where the files are

Other publishers' files are linked, not hosted. "verify" = check the license at the link before commercial use.

Wikiwand (Wikipedia)IEC 60228: the standard cross-sectional areas 0.5 to 2500 mm2 and the conductor classeswebPublisher's page; dimensions are facts
myElectricalStandard cable and wire sizes (IEC 60228): metric sizes and the metric-to-AWG table with strand counts and overall diameterswebPublisher's page; dimensions are facts

Xem scan

File coming

No downloadable true-size file yet: the published figures do not fix the whole shape, and Xem never guesses a number. A measured scan is planned; request it and it moves up.

Let your AI pull this. Add https://xemstudio.com/mcp to Claude, ChatGPT, Cursor or any MCP client (free, no account, one minute) and it can look up exact sizes, mating fits and free STEP/STL from every chat.
Set it up →

Plain text: sheet.txt · JSON: /api/geometry?object=metric-wire-sizes-iec-60228-mm2-awg

Schematic, not to scale.

Fits with

Questions

What is the diameter of a 2.5 mm² conductor?

1.80 mm solid, or 2.06 mm overall for 7 strands of 0.686 mm (myElectrical's table).

What AWG is 1.5 mm²?

Between 15 and 16 AWG: 15 AWG is 1.65 mm² and 16 AWG is 1.31 mm² (ASTM B258).

What sizes does IEC 60228 list?

0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630, 800, 1000, 1200, 1400, 1600, 1800, 2000, 2500 mm².