Library › Electronic components › Connectors ·

DIN-rail terminal blocks Phoenix UT, ST and UK: width per pole 5.2 / 6.2 / 8.2 / 10.2 mm, height on the rail, wire range, strip length

How wide is a DIN-rail terminal block per pole, and what wire does a UT 2,5, UT 4, ST 2,5 or UK 5 N take? · Standard part · basis: Phoenix Contact datasheets for nine feed-through blocks (UT, ST and UK families) as hosted by Farnell, Chipdip, corys.co.nz and phoenixcontact.com; numbers only

Also called: ut 2,5 terminal block width, phoenix ut 4 dimensions, st 2,5 terminal block width 5.2 mm, din rail terminal block dimensions, terminal block width per pole, uk 5 n width 6.2 mm, ut 10 terminal height ns 35, phoenix contact 3044076 dimensions, 3031212 st 2,5 height, terminal block wire range 2.5 mm2 4 mm2 6 mm2 10 mm2, din rail terminal block 5.2 mm, ut 6 8.2 mm, end cover width terminal block

Exact dimensions. True size, with no tolerance added.

sizes
9 in table

Notes

  • Width per pole read from the sheets: 5.2 mm (2.5 mm2 class: UT 2,5, ST 2,5), 6.2 mm (4 mm2 class: UT 4, ST 4, UK 5 N), 8.2 mm (6 mm2 class: UT 6, ST 6) and 10.2 mm (10 mm2 class: UT 10, UK 10 N). A block's end cover adds 2.2 mm (UT / ST) or 1.8 mm (UK). A row of n blocks measures n x width plus one end cover.
  • Heights are shown on the rail the sheet names: NS 35/7,5 (7.5 mm deep DIN rail) and NS 35/15 (15 mm). The UT sheets also print a single 'height 46.9' without a rail; the UK 5 N sheet prints one height (42.5) and its depth on each rail. The columns follow each sheet; 'length' is what Phoenix prints as length (47.7 for UT, 42.5 for UK 10 N) and is not the same measurement across families. Rail dimensions are on din-rail-35mm.
  • Wire range, strip length and nominal current / voltage are as printed in the sheet's connection data. The UT 6 BU and UT 10 sheets list the end cover as the D-UT 2,5/10 cover (2.2 mm). The ST 2,5 sheet prints the flexible AWG maximum as 14 in one table and 12 in another; both are noted. Ratings are the sheet's nominal values, not a design limit for your installation.
  • Not read: UT 16, ST 10, ST 16, UK 2,5 N, UK 6 N, UK 16 N and the other variants (double-level, PE, fused). The 'width per pole' sequence above is read from the nine families listed; it is not asserted for blocks not read.
  • No file: the block outline (latch, foot, screw access) is not published as numbers in the sheets. Phoenix publishes per-part STEP on its product pages (linked, not copied).

DIN-rail terminal blocks Phoenix UT, ST and UK: width per pole 5.2 /… size chart

typeorder no.width per pole (mm)end cover width (mm)height on NS 35/7,5 (mm)height on NS 35/15 (mm)length / height / depth as printed (mm)solid mm2 (AWG)flexible mm2strip (mm)nominal current / voltage
UT 2,5 (screw)30440765.22.247.555length 47.7; height 46.90.14-4 (26-12)0.14-4924 A / 1000 V
UT 4 (screw)30441026.22.247.555length 47.7; height 46.90.14-6 (26-10)0.14-6932 A (4 mm2) / 1000 V
UT 6 BU (screw)30441448.22.2 (D-UT 2,5/10 cover)47.555length 47.70.2-10 (24-8)0.2-10 stranded1041 A / 1000 V
UT 10 (screw)304416010.22.2 (D-UT 2,5/10 cover)47.555length 47.70.5-16 (20-6)0.5-16 stranded1057 A / 1000 V
ST 2,5 (spring-cage)30312125.22.236.544length 48.50.08-4 (28-12)0.08-2.5 (28-14; one table prints 12)8-1024 A (2.5 mm2) / 800 V
ST 4 (spring-cage)30313646.22.236.544length 560.08-6 (28-10)0.08-48-1032 A / 800 V
ST 6 (spring-cage)30314878.22.2 (D-ST 6 cover)43.551length 69.50.2-10 (24-8)0.2-6 stranded1241 A / 1000 V
UK 5 N RD (screw)30266966.21.8— (one height)—height 42.5; depth 47 (NS 35/7,5), 54.5 (NS 35/15), 52 (NS 32)0.2-6 (24-10)0.2-4 (24-12)832 A / 800 V
UK 10 N BU (screw)300508610.21.847.354.8length 42.50.5-16 (20-6)0.5-10 (20-8)1057 A / 800 V

Where the files are

Other publishers' files are linked, not hosted. "verify" = check the license at the link before commercial use.

Phoenix Contact (Farnell copy of the UT 2,5 3044076 sheet)UT 2,5 feed-through terminal block: width 5.2 mm, end cover 2.2 mm, length 47.7, height 46.9 / NS 35/7,5 47.5 / NS 35/15 55 mmwebPublisher's page; dimensions are facts
Phoenix Contact (Chipdip copy of the UT 4 3044102 sheet)UT 4 feed-through terminal block: width 6.2 mmwebPublisher's page; dimensions are facts
Phoenix Contact (Farnell copy, UT 6 BU 3044144)UT 6 BU: width 8.2 mm, 0.2 to 10 mm2webPublisher's page; dimensions are facts
Phoenix Contact (Farnell copy, UT 10 3044160)UT 10: width 10.2 mm, 0.5 to 16 mm2webPublisher's page; dimensions are facts
Phoenix Contact (corys.co.nz copy of the ST 2,5 3031212 sheet)ST 2,5 spring-cage feed-through: width 5.2 mm, length 48.5, heights 36.5 / 44 mmwebPublisher's page; dimensions are facts
Phoenix Contact (Chipdip copy of the ST 4 3031364 sheet)ST 4: width 6.2 mm, length 56, heights 36.5 / 44 mmwebPublisher's page; dimensions are facts
Phoenix Contact (Chipdip copy of the ST 6 3031487 sheet)ST 6: width 8.2 mm, length 69.5, heights 43.5 / 51 mmwebPublisher's page; dimensions are facts
Phoenix Contact (UK 5 N RD 3026696 sheet)UK 5 N RD: width 6.2 mm, end cover 1.8 mm, height 42.5, depth 47 / 54.5 / 52 mmwebPublisher's page; dimensions are facts
Phoenix Contact (Chipdip copy of the UK 10 N BU 3005086 sheet)UK 10 N BU: width 10.2 mm, end cover 1.8 mm, length 42.5, heights 47.3 / 54.8 mmwebPublisher's page; dimensions are facts
Phoenix ContactPhoenix Contact terminal block product pages carry per-part CAD (example page: UT 2,5-MTD)STEP, PDFPhoenix Contact site terms verify

Xem scan

File coming

No downloadable true-size file yet: the published figures do not fix the whole shape, and Xem never guesses a number. A measured scan is planned; request it and it moves up.

Let your AI pull this. Add https://xemstudio.com/mcp to Claude, ChatGPT, Cursor or any MCP client (free, no account, one minute) and it can look up exact sizes, mating fits and free STEP/STL from every chat.
Set it up →

Plain text: sheet.txt · JSON: /api/geometry?object=din-rail-terminal-blocks-phoenix-ut-st-uk

length
Schematic, not to scale.

Fits with

Questions

How wide is a UT 2,5 terminal block?

5.2 mm per pole, end cover 2.2 mm, 0.14 to 4 mm2 (26 to 12 AWG), strip 9 mm (Phoenix 3044076).

What is the width of a 6 mm2 DIN-rail terminal block?

8.2 mm for UT 6 and ST 6 (Phoenix 3044144 and 3031487), wire 0.2 to 10 mm2 solid.

How tall is a spring-cage ST 2,5 on a DIN rail?

36.5 mm on NS 35/7,5 and 44 mm on NS 35/15 (Phoenix 3031212).